MK-S default

Gas ceramic infrared heater MKS

Heating surface: perforated ceramic plaques 135 x 97 mm creating heating surface according to needs
one or two plaques' rows
Reflector: polished stainless steel, optimalized shape for even suspension
Fuel: natural gas NG
Nominal thermal output: 6,7 up to 40,6 kW
Dimensions: layout dimensions (0,8 x 0,4) m  up to  (1,5 x 0,5) m, height 0,25 mm

Surface temperatures:

  • on the ceramic plaques up to 900 °C
  • on the reflector up to 150 °C
  • can be considered as point heat source - high intensity on small surface

 

Control possibilities:

  • manual control ROT-1 (ON/OFF), can be fitted with time relay
  • control box RA-T for more appliances, week program with manual switch for each appliance
  • free programmable controller for example with visualisation on PC
  • to ensure low consumption it is necessary to use globe temperature sensor and controllers allowing external sensors!

Detail MKS

Detail zářiče MK-S

1 - perforated ceramic plaques
2 - mesh from austenitic steel increasing efficiency
3 - optimized reflector from stainless steel polished metal sheet
4 - mixing chamber, special high temperature surface treatment
5 - suspension holes, S-hooks included in heater's delivery connectable to whatever suspension system
6 - suspension system (wire or nodal chain with adjusting screw)

DIMENSIONS

MKS 7 up to 18 kW

A (mm) B (mm)
MKS 7 458 413
MKS 11 652 607
MKS 15 846 801
MKS 18 1040 995
MKS 7 - 18 kW

MKS 25 up to 43 kW

A (mm) B (mm)
MKS 25 794 704
MKS 36 1040 995
MKS 43 1234 1189
MKS 25 - 43 kW

TECHNICAL PARAMETERS

 

One stage Unit MKS 7.1
MKS 11.1 MKS 15.1 MKS 18.1 MKS 25.1 MKS 36.1 MKS 43.1
Nominal thermal output kW 6,7 10,9 14,8 17,5 24,0 34,0 40,6
Gas consumption NG m3/h 0,75 1,21 1,65 1,95 2,67 3,78 4,52

 

Two stage Unit MKS 7.2 MKS 11.2 MKS 15.2 MKS 18.2 MKS 25.2 MKS 36.2 MKS 43.2
Nominal thermal output
min. / max.
kW 4,0/6,7 6,5/10,9 8,9/14,8 10,5/17,5 14,4/24,0 20,4/34,0 24,4/40,6
Gas consumption NG
min. / max.
m3/h 0,45/0,75 0,72/1,21 1,00/1,65 1,17/1,95 1,60/2,67 2,27/3,78 2,71/4,52

 

Number of plaques - 4 6 8 10 2 x 7 2 x 10 2 x 12
Surface temperature °C 800 up to 900
NG overpressure
min./max. (G20)
kPa 2 / 5
Weight kg 6,6 7,6 8,6 12,1 14,6 17,6 20,6
Gas hose connection inch G 1/2"
Gas hose - couplings - union nut G1/2" / external thread R1/2"; length 1 m
Electro 230V/50Hz - 20W / IP40