Radiant panel KSP KIT
Basic element: | aluminium module 330 mm wide |
Construction: | precise steel tube Ø 18 mm, embedded in aluminum heating surface |
Thermal insulation: | 30 mm thick with alluminum coating |
Panel composition: | modules are suspended on common crossbars |
Lengths: | 2, 3, 4, 6, m |
Connecting of panels into bands: | pressfittings DN 18, V contour |
Hydraulic variants: | paralell, half paralell - with pressable header |
Heat transfer medium:
- warm water up to 120 °C (PN 6)
Control possibilities:
- Three way valve + circulation pump
- Two way valve + circulation pump
- Jet pump + controller with optimisation
Detail KSP KIT
1 - aluminium heating surface
2 - precise carbon steel tube
3 - mineral insulation with aluminium coating
4 - top aluminium coating
5 - common top crossbar
6 - carabine 50 x 5
7 - suspension system (wire or nodal chain with adjusting screw)
DIMENSIONS - LENGTH
Radiant panel KSP KIT - 2 m

Radiant panel KSP KIT - 4 m

Radiant panel KSP KIT - 3 m

Radiant panel KSP KIT - 6 m

DIMENSIONS - WIDTH
Radiant panel KSP KIT I - 6 m

Radiant panel KSP KIT III - 6 m

Radiant panel KSP KIT II - 6 m

Radiant panel KSP KIT IV - 6 m

WEIGHTS AND SUSPENSIONS
Total width [mm] n x 150 |
Weight [kg] | Load/hanger | Water volume | Suspensions [pcs] | |||||||||
Panel L = 2 m | Panel L = 3 m | Panel L = 4 m | Panel L = 6 m | [kg] | [l/m] | Length of panel [m] | |||||||
Operation | Assembly | Operation | Assembly | Operation | Assembly | Operation | Assembly | 2 or 3 | 4 or 6 | ||||
330 | 9,0 | 7,1 | 13,4 | 10,7 | 17,9 | 14,2 | 26,8 | 21,3 | 2,3 - 6,6 | 0,8 | 4 | 6 | |
720 | 19,4 | 14,2 | 28,2 | 21,4 | 37,8 | 28,4 | 55,9 | 42,6 | 4,9 - 13,7 | 1,6 | 4 | 6 | |
1110 | 29,1 | 21,3 | 42,3 | 32,1 | 56,8 | 42,6 | 83,5 | 63,9 | 7,3 - 20,5 | 2,4 | 4 | 6 | |
1500 | 38,8 | 28,4 | 56,4 | 42,8 | 75,8 | 56,8 | 111,4 | 85,2 | 9,7 - 27,3 | 3,2 | 4 | 6 |
In the operation weight there is weight of panels , common crossbars and water content. In the weight there is no weight of any suspension material to the ceiling as it depends on specification and dimensions.
THERMAL OUTPUTS - HEATING EN 14037-2
Dt [K] |
KIT I | KIT II | KIT III |
KIT IV | ||||
Panel | Headers | Panel | Headers | Panel | Headers | Panel | Headers | |
[W/m] | [W/pair] | [W/m] | [W/pair] | [W/m] | [W/pair] | [W/m] | [W/pair] | |
20 | 69 | 11 | 138 | 22 | 208 | 34 | 277 | 45 |
25 | 90 | 15 | 181 | 30 | 271 | 45 | 361 | 59 |
30 | 112 | 19 | 225 | 37 | 337 | 56 | 450 | 75 |
35 | 135 | 23 | 270 | 46 | 405 | 68 | 541 | 91 |
40 | 159 | 27 | 317 | 54 | 476 | 81 | 634 | 108 |
45 | 183 | 31 | 365 | 63 | 548 | 94 | 370 | 125 |
50 | 207 | 36 | 414 | 72 | 621 | 107 | 828 | 143 |
55 | 232 | 40 | 464 | 81 | 696 | 121 | 928 | 161 |
60 | 258 | 45 | 515 | 90 | 773 | 135 | 1030 | 180 |
65 | 283 | 50 | 567 | 100 | 850 | 150 | 1134 | 200 |
70 | 310 | 55 | 620 | 110 | 929 | 164 | 1239 | 219 |
75 | 336 | 60 | 673 | 120 | 1009 | 179 | 1346 | 239 |
80 | 363 | 65 | 727 | 130 | 1090 | 195 | 1454 | 260 |
Δt = (tm1 + tm2) / 2 - ti where: tm1 [°C] water temperature - inlet | tm2 [°C] water temperature - return | ti [°C] internal design temperature
PRESSABLE HEADERS
Header 2+1, 128 mm - 213.059

Header 4+0, 295 mm - 213.060

Header 6+1, 521 mm - 213.068

Header 4+1, 295 mm - 213.062

Header 4+0, 350 mm - 213.061

Header 12+0, 1079 mm - 213.065

Header 8+1, 684 mm - 213.064

Header 8+0, 684 mm - 213.063

Header 12+1, 1079 mm - 213.066